Earthing Shielded Cat6 on Site: A Rigger's Checklist

10 Nov 2026 · By Jeremy Melhop

Shielded Cat6 run up a tower or across a site is only as good as its earthing. The shield or steel armour is there to carry unwanted current away, and it can only do that if it is bonded properly at the right points. This is a practical checklist for riggers and installers running earthable Cat6 outdoors. It is a general guide, not a design: always follow the site design, the carrier or asset owner's standards and the equipment maker's instructions, and where they differ from anything here, they win.

1. Check the design before you cut anything

Earthing points, bonding bars and the number of earth kits per run are set by the site design and the standards your client works to. Before you start, find out where each run must be earthed, which earth bar each kit lands on, and whether the equipment end needs anything extra. If the drawings are unclear, ask before the cable goes up, not after.

2. Use cable that can actually be earthed

Plain outdoor Cat6 has nothing to earth. For runs that need bonding, use cable with a shield or steel armour designed to be earthed, such as our shielded earthable Cat6, and terminate it with shielded RJ45 plugs so the shield is carried through at the connector where the equipment is designed for it.

3. Pick the right earth kit

A Cat6 earth kit clamps onto the exposed shield or armour and gives you a lead to land on the earth bar. Our Cat6 earth kits come in mesh loop and copper clamp styles. Whichever you use, make sure it suits the cable diameter and the shield type, and that it is designed for outdoor use.

4. Strip carefully

Remove only as much jacket as the kit needs. Do not nick the shield or cut into the pairs, and keep the shield clean and undamaged where the kit makes contact. A rushed strip is the most common reason an earth kit ends up loose or ineffective.

5. Fit the kit and weatherproof it

Fit the kit as its instructions describe, with a firm, even contact on the shield. Then weatherproof the joint so water cannot get under the jacket. A standard approach is a layer of mastic to seal it, wrapped with good electrical tape over the top, but follow the kit maker's instructions and the site standard. Water that gets in at an earth kit can travel along the cable and cause problems well away from the joint.

6. Land the lead on the earth bar

Run the earth lead to the nominated earth bar by a short, direct path with no tight bends, and avoid running it back up the structure. Use a crimped tinned copper lug sized for the lead, clean the contact surfaces, and torque the fixing to the site standard. Many sites also want a dab of anti-corrosion compound on the joint.

7. Secure and label the run

Support the cable with clips or stainless steel ties at the spacing the site calls for, so the weight of the run is not hanging off the earth kit or the connector. Label both ends and note the earth points on your as-built records.

8. Test and photograph

Test the cable once it is terminated and earthed, and record the results. Take clear photos of each earth kit, the earth bar connections and the labelling before you leave. Most clients ask for them, and they save a trip back up when someone asks how a run was done.

Quick checklist

  • Earth points confirmed on the design
  • Earthable shielded Cat6 and shielded plugs
  • Correct earth kit for the cable
  • Clean strip, shield undamaged
  • Kit weatherproofed
  • Short, direct lead to the right earth bar, lugged and torqued
  • Run supported, labelled, tested and photographed

Short on kits for a job?

Cat6 earth kits and feeder earth kits are in stock in Brisbane. Standard delivery is $15 per order, free over $300, and in-stock items can go super express: we fly the gear to the nearest airport and drive it to your site, at a fixed price by zone, Australia wide. Send your list through the quote form or call 0422 999 583.